Air handling unit JAWAR R200
Chimney accessoriesAir handling unit JAWAR R200 is a compact ventilation central unit used for mechanical ventilation systems in small residential buildings. It is a Polish product, based on components from leading European producers.
Air handling unit JAWAR R200 is a compact ventilation central unit used for mechanical ventilation systems in small residential buildings. It is a Polish product, based on components from leading European producers.. Capacity: 200 m3/h; heat exchanger Recair; fans EBM Papst; 3-stage steering; energy efficiency class B
Product index: RR200
Feature | Unit | R200 | R350 | R450 |
Maximum flow rate | m3/h | 405 | 510 | 795 |
Pressure at nominal flow | Pa | 120 | 250 | 300 |
Energy consumption | W | 88-120 | 11-175 | 44-320 |
Power supply | V | 230 | 230 | 230 |
Outlet diameter | mm | 125 | 160 | 160 |
Length/Width/Hight | mm | 760/280/650 | 800/480/650 | 800/580/650 |
Weight | kg | 33 | 45 | 45 |
Filter class | – | G4 | G4 | G4 |
Outlet arrangement | – | horizontal | horizontal | horizontal |
SEC in average climate conditions | kWh/m2/yr | -31,44 | -38,58 | -39,46 |
SEC in cold climate conditions | kWh/m2/yr | -69,04 | -76,19 | -77,07 |
SEC in warm climate conditions | kWh/m2/yr | -7,27 | -14,41 | -15,29 |
SEC class (average climate conditions) | – | B | A | A |
Declared type | – | two-way | two-way | two-way |
Motor & drive | – | Variable speed fan | Variable speed fan | Variable speed fan |
Heat recovery type | – | membrane | membrane | membrane |
Efficiency acc. to UE 1254/2014, dT=13°C, SWM | % | 85 | 85,3 | 85,3 |
Power input at max air flow | W | 119,7 | 174,1 | 318,9 |
Sound power level | dB (A) | 43-55 | 36-58 | 36-60 |
Reference flow rate | m3/s | 0,08 | 0,09 | 0,09 |
Reference pressure difference | Pa | 50 | 50 | 50 |
Specific Power Input | W/(m3/h) | 0,49 | 0,22 | 0,19 |
Ventilation control | – | 0,85; central demand control | 0,85; central demand control | 0,85; central demand control |
Maximum internal leak | % | 2 | 2 | 2 |
Maximum external leak | % | 3 | 3 | 3 |
Clogged filter warning | – | Yes | Yes | Yes |
Assembly / disassembly instructions | – | jawar.com.pl | jawar.com.pl | jawar.com.pl |
Annual heating saved in average climate conditions | kWh/m2 | 45 | 45 | 45 |
Annual heating saved in cold climate conditions | kWh/m2 | 88 | 88 | 88 |
Annual heating saved in warm climate conditions | kWh/m2 | 20 | 20 | 20 |
Select a chimney